Single Phase Multifunction Reference Energy Meter (0.05/0.1) (HC3101H)

Product Description

Single Phase Multifunction Reference Energy Meter(0.05/0.1) HC3101H

 



1. Features

1.1 HC3101A single phase multifunction reference meter is the intelligent high accuracy reference meter using high accuracy ADC and DSP high speed processor as its core.

1.2 It can simultaneously measure and display three phase voltage (V), current (A), active power (W), reactive power (var), frequency (Hz), power factor (PF), phase angle (θ), apparent power (S) and other power, and output active or reactive energy pulses;

1.3 Harmonic analysis function: can choose voltage,current input signal to analysis , and can display the content of 2-21 times harmonic.

1.4 Using LCD English display interface, clear picture, with six display digits, is easy to operate, and the function is easy to set, is a smart electrical measuring instruments;

1.5 Using automatic compensation technology, to achieve the high accuracy of the relative error which is better than 0.05% RD.

1.6 Energy meter error test function;

1.7 With RS-232 communication port,can directly connect with the PCand provide the data to PC;also the functions of HC3101A can be completely controlled by PC,make the full auto test comes true.

2. Specification

2.1 Voltage range:220V (50~300V)
2.2 Current range:0.1A/1A/10A/100A
2.3 Accuracy:0.05/0.1(look accuracy table)
2.4 Working environment:temperature:0ºC~40ºC,relative humidity:35%~85%
2.5 Temperature affect:(0ºC~40ºC)voltage,current,frequency< 15ppm/ºC, power<30ppm/ºC
2.6 Assistant power supply: AC220 V ± 15 % ,45Hz ~ 65Hz, 15VA
2.7 Volume: length× width× height   483mm × 420mm ×134mm
2.8 Weight:12kg

Accuracy Table(3101A)

parameter range accuracy
0.05 0.1
voltage 50~300V 0.05%RD 0.1%RD
current 0.1A~120A 0.05%RD 0.1%RD
active power 0.1~120A,50~300V,PF>=0.5 0.05%RD 0.1%RD
reactive power 0.1~120A,50~300V,PF>=0.5 0.1%RD 0.2%RD
active energy 0.1~120A,50~300V,PF>=0.5 0.05%RD 0.1%RD
reactive energy 0.1~120A,50~300V,PF>=0.5 0.1%RD 0.2%RD
factor -1.0  ~   0  ~  1.0 0.0005 0.001
frequency 45Hz~65Hz 0.01Hz 0.01Hz
phase 0~360°(U> 50V, I> 0.1A) 0.1° 0.2 °